TRIOL AT24 line UB

Place an order
vfd, variable frequency drive, vfd drive, industrial automation, automation companies, low voltage

Distinctive benefits

Control type

Vector sensorless (open-loop) control

Motor parameters

Auto-tuning

Built-in

PID-controller

Multi-stage speed control

16 steps

4 parameter sets

Acceleration and deceleration time

About product

Simple, reliable and cost-effective solution

Variable Frequency Drive Triol AT24 line UB is a basic solution for common process tasks with simple installation, quick commissioning and easy operating. AT24 UB is simple, reliable and cost-effective solution to control pumps and HVAC systems. The integrated terminal allows making settings without additional equipment and service software.

Specifications

Input 

Input voltage, V       

3х380 / 3х480/ 3×690 (-15 % …+10 %)

Input frequency, Hz

50 / 60 (-5 %…+5 %)

Output  

Output current, A  

1.2 … 110

Output frequency, Hz   

0.5…400

Frequency resolution, Hz  

0.1

Acceleration / deceleration time, s

1 …36000

Overcurrent characteristics

120 % of rated value for 60 sec

Efficiency, %

>97

Motor control  

Control methods  

V/f (volts-per-hertz) (5 reference point) sensorless vector control (open-loop) sensor vector control (close-loop)

PWM frequency, kHz

2…10

Speed range  

1:100 in open-loop system 1:1000 in closed-loop system

Speed accuracy (static)

±10% of motor nominal slip in open-loop system ±0.1 % of rated speed in close-loop system

Torque accuracy   

±10% in open-loop system ± 5 % in close-loop system

Braking   

By frequency

Coasting    

Dynamic   

Acceleration / deceleration types

S-curve, linear (3 reference points)

Interface  

Terminal  

Integrated seven-segment

Light alarm 

“Ready”; “Run”; “Control channel”, “Rotation”

Push buttons 

“Start”; “Stop”; “Fast access “

Control signals  

Customer supply

10 V DC, up to 30 mA 24 V DC, up to 150 mA

Number of discrete inputs

7

Discrete inputs

2 Dl “Direction of rotation” by default 4 Dl programmable 1 Dl high speed pulse input

Discrete inputs type

24 V

Number of relay outputs

2

Relay outputs type

250 V, 1 A

Discrete output   

1 DO high speed or open collector

Number of analog inputs

2

Analog inputs

1 Al 0…10 V by default 1 Al programmable 0…10 V or 0…5 mA or 4…20 mA

Number of analog outputs

2

Analog outputs    

Programmable 0…10 V or 0…5 mA or 4…20 mA

Communication  

Physical Interface

2 wire RS-485 for Modbus

Communication protocols

Modbus RTU

Frame transmission  

19200 bps by default 1200, 2400, 4800, 9600,19200, 38400 bps

Data format

8 bits, 1 stop bit, no parity

Number of addresses 

1…247 for Modbus

Access 

Slave

Protection

Supply protections 

Phase loss

Motor protections   

Overload Phase loss

VFD protections 

Overload, Overheating, DC-link undervoltage, DC-link overvoltage, Power switch failure

Insulation  

Galvanic isolation between power and user circuits

Insulation resistance  

>1 MQ

Configuration  

Braking IGBT-chopper 

Up to 15 kw: built-in From 18 kW: option, built-in

Optional equipment 

Braking resistors 

Option, outdoor, by request   

Input line choke 

Option, outdoor, by request 

Input EMC filter (C2)

Option, outdoor, by request 

Output dV/dt filter

Option, outdoor, by request 

Construction 

Protection degree of Enclosure

IP21

Cabinet material  

Up to 7.5 kw: plastic From 11 kW: steel

Cooling 

Forced air 

Noise level, @ 1 m, dB(A) 

<75

Installation 

Wall mounting 

Maintenance 

One-side   

Cable entry 

Bottom

Operating conditions 

Operating conditions 

Indoor, no caustic and volatile air, no dust

Operating temperature 

-10…+40 °C (-10…+104 F)

Storage temperature 

-40…+50 °C (-40…+122 F)

Relative humidity, %

from 5 to 90 non condensing

Altitude, m 

up to 1000 m – rated power above 1000 m – with reduced power

Functions

  • Start / stop / reverse of motor with set acceleration and deceleration rates
  • Auto-tuning of motor parameters
  • PID-controller
  • 2-wire control
  • 3-wire control
  • Automatic restart  
  • Accelerated passing of resonant frequencies (2 ranges)
  • Simple PLC and multi-step speed control with 16 steps and 4 acceleration / deceleration times
  • Recording the last 3 reasons of failures